AWG to mm² formula
For gauge n, the solid-equivalent conductor diameter d in millimetres and area A in square millimetres are:
A = π × d² / 4
Use n = 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0. The diameter describes an equivalent solid circular conductor, not the outside diameter of an insulated or stranded cable.
Worked example: 10 AWG
10 AWG gives a diameter of approximately 2.588 mm and an area of 5.261 mm². A nominal 6 mm² conductor has more area, but the sizes are not identical and are not automatically interchangeable.
AWG to mm² conversion chart
| AWG | Area (mm²) | Equivalent diameter (mm) |
|---|---|---|
| 4/0 | 107.2193 | 11.6840 |
| 3/0 | 85.0288 | 10.4049 |
| 2/0 | 67.4309 | 9.2658 |
| 1/0 | 53.4751 | 8.2515 |
| 2 | 33.6308 | 6.5437 |
| 4 | 21.1506 | 5.1894 |
| 6 | 13.3018 | 4.1154 |
| 8 | 8.3656 | 3.2636 |
| 10 | 5.2612 | 2.5882 |
| 12 | 3.3088 | 2.0525 |
| 14 | 2.0809 | 1.6277 |
| 16 | 1.3087 | 1.2908 |
| 18 | 0.8230 | 1.0237 |
| 20 | 0.5176 | 0.8118 |
| 22 | 0.3255 | 0.6438 |
| 24 | 0.2047 | 0.5106 |
| 26 | 0.1288 | 0.4049 |
| 28 | 0.0810 | 0.3211 |
| 30 | 0.0509 | 0.2546 |
| 32 | 0.0320 | 0.2019 |
| 34 | 0.0201 | 0.1601 |
| 36 | 0.0127 | 0.1270 |
| 38 | 0.0080 | 0.1007 |
| 40 | 0.0050 | 0.0799 |
Does the nearest gauge carry the same current?
No. Area conversion is geometric. Ampacity also depends on material, insulation, installation method, ambient temperature, grouping, terminals and applicable local rules. This converter does not select a safe installation size.
How does reverse conversion work?
The reverse mode shows the nearest AWG by gauge number and separately identifies an AWG whose calculated area is at least the input area. A nearest gauge can have less area than the entered metric size. Neither result is an installation recommendation.