Wire sizes

AWG vs mm²: understanding wire size conversions

Why wire gauge and metric area are different systems, how to convert them, and why nearest sizes are not always equivalent.

CableFormula editorial · · 5 min read

AWG describes a logarithmic series of conductor sizes. Square millimetres (mm²) describe cross-sectional area directly. A conversion connects the geometry; it does not establish that two cable products meet the same requirements.

Open the AWG to mm² converter to compare values while reading.

Why a smaller AWG number means a bigger wire

The AWG sequence increases conductor diameter as the gauge number falls. Its geometric definition uses 0.005 inches at 36 AWG and 0.46 inches at 4/0 AWG. In millimetres, the diameter formula is:

d = 0.127 × 92^((36 − n) / 39)

The area is π × d² / 4. For 1/0 use n = 0; for 2/0, 3/0 and 4/0 use −1, −2 and −3.

Example: 10 AWG and 6 mm²

10 AWG has a calculated area of approximately 5.261 mm². A nominal 6 mm² conductor is larger by about 14% when comparing those area numbers. It is not an exact conversion.

For 12 AWG the calculated area is approximately 3.309 mm². A commonly listed nominal metric size above this value is 4 mm², but calling the two sizes equivalent hides a meaningful difference.

Nearest is different from at least

When converting 6 mm² back to AWG, the nearest gauge by the continuous gauge formula is 9 AWG, approximately 6.634 mm². For another metric input, the nearest gauge may have less area than requested. Our converter reports the nearest result and a separate gauge with at least the entered area.

Neither result is a recommendation to install that wire. Gauge availability also varies by supplier and product.

Area is not outside diameter

Conductor area excludes insulation and sheath. For stranded conductors, the equivalent solid diameter does not describe the physical bundle diameter because strands leave gaps and may be compacted. Insulated cable outside diameter must come from the manufacturer’s datasheet.

What conversion cannot tell you

A matching area does not settle ampacity, voltage rating, flexibility, temperature rating, terminal compatibility or local compliance. Those questions require the actual cable construction and installation conditions.

For a copper material estimate, use the converted area in the copper weight calculator.

Reference and method

Compare calculated values with Multi/Cable’s AWG cross-reference. Rounded reference values can differ slightly from an unrounded formula result. Our methodology explains the distinction between geometric estimates and installation design.